China Best Voltage Tester Meter Manufacturers – CC1 Series AC Contactor for 9-95A – Changan Group
China Best Voltage Tester Meter Manufacturers – CC1 Series AC Contactor for 9-95A – Changan Group Detail:
Description
Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 95A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1. IEC/EN 60947-5-1.
Control Coil Voltage(AC Coil Operation)
| Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
| Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
|
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
|
Control Coil Voltage(DC Coil Operation)
|
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
|
Code |
JD |
BD |
CD |
ED |
FD |
MD |

Technical Specification
| Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
| Model No. |
CC1-09 |
CC1-12 |
CC1-18 |
CC1-25 |
CC1-32 |
|
| Rated Conventional Heating Current |
Ith (A) |
20 |
20 |
32 |
40 |
50 |
| Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
| Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
9 |
12 |
18 |
25 |
32 |
|
AC-4 Ie(A) |
3.5 |
5 |
7.7 |
8.5 |
12 |
|
| Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
2.2 |
3 |
4 |
5.5 |
7.5 |
|
380/415V KW |
4 |
5.5 |
7.5 |
11 |
15 |
|
|
660/690V KW |
5.5 |
7.5 |
10 |
15 |
18.5 |
|
| Electrial life(x103 operations) |
AC-3 |
1000 |
1000 |
1000 |
1000 |
800 |
|
AC-4 |
200 |
200 |
200 |
200 |
200 |
|
| Mechanical life(x106 operations) |
10 |
10 |
10 |
10 |
8 |
|
| Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
|
A |
20 |
20 |
32 |
40 |
50 |
|
| Main circuit |
3P or 4P |
|||||
| Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A | 1NO or 1NC | |||||
| Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
| Model No. |
CC1-40 |
CC1-50 |
CC1-65 |
CC1-80 |
CC1-95 |
|
| Rated Conventional Heating Current |
Ith (A) |
60 |
80 |
80 |
100 |
125 |
| Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
| Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
40 |
50 |
65 |
80 |
95 |
|
AC-4 Ie(A) |
18.5 |
24 |
28 |
37 |
44 |
|
| Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
11 |
15 |
18.5 |
22 |
25 |
|
380/415V KW |
18.5 |
22 |
30 |
37 |
45 |
|
|
660/690V KW |
30 |
33 |
37 |
45 |
45 |
|
| Electrial life(x103 operations) |
AC-3 |
800 |
600 |
600 |
600 |
600 |
|
AC-4 |
150 |
150 |
150 |
100 |
100 |
|
| Mechanical life(x106 operations) |
8 |
8 |
8 |
6 |
6 |
|
| Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
|
A |
63 |
80 |
80 |
100 |
125 |
|
| Main circuit |
3P or 4P |
|||||
| Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A |
1NO+1NC |
|||||
| Model |
Cabling cross section(Cu) |
screw size | Tightening torque(N.m) | |||
| Number of piece |
Flexible cable with cold-pressed socket(mm2 ) |
Flexible cable without cold- pressed socket(mm2 ) |
Inflexible cable(mm2 ) | |||
| CC1-09 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
| CC1-12 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
| CC1-18 |
1~2 |
4 |
6 | 6 |
M3.5 |
0.8 |
| CC1-25 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
|
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
| CC1-32 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
|
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
| CC1-40 |
1 |
10 |
16 | 10 |
M4 |
3.5 |
|
2 |
10 |
10 | 10 |
M8 |
3.5 |
|
| CC1-50 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
|
2 |
16 |
16 | - |
M8 |
3.5 |
|
| CC1-65 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
|
2 |
16 |
16 | - |
M8 |
3.5 |
|
| CC1-80 |
1 |
50 |
50 | 50 |
M8 |
3.5 |
|
2 |
25 |
35 | - |
M10 |
4.0 |
|
| CC1-95 |
1 |
50 |
50 | 50 |
M10 |
4.0 |
|
2 |
25 |
35 | - |
M10 |
4.0 |
|


1.L: in main circuit, the distance between terminals and plate;
2.P: in main circuit, the distance between two phases;
3.S: in main circuit, the width of contacting plate.
| Model |
A max |
B max |
C max |
D max |
E max |
a |
b |
Φ |
L |
P |
S |
| CC1-09(Z)~12(Z) |
47 |
76 |
82(116) |
120.5(154.5) |
140.5(174.5) |
34/35 |
50/60 |
4.5 |
60(95) |
10.5 |
8.6 |
| CC1-18(Z) |
47 |
76 |
87(122) |
125.5(160.5) |
145.5(180.5) |
34/35 |
50/60 |
4.5 |
61(96) |
11.3 |
10.4 |
| CC1-25(Z) |
57 |
86 |
95(131) |
133.5(169.5) |
153.5(189.5) |
40 |
48 |
4.5 |
70(107) |
13.2 |
11.7 |
| CC1-32(Z) |
57 |
86 |
100(138) |
138.5(176.5) |
158.5(196.5) |
40 |
48 |
4.5 |
71.6(120) |
14.5 |
13 |
| CC1-4011(Z)~6511(Z) |
77 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
| CC1-4004/4008(Z)~6504/6508(Z) |
84 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
| CC1-8011(Z)~9511(Z) |
87 |
129 |
127(188) |
165.5(226.5) |
185.5(246.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
| CC1-8004/8008(Z)~9504/9508(Z) |
96 |
129 |
127(183) |
160.5(221.5) |
180.5(241.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
Product detail pictures:
Related Product Guide:
We've got a highly efficient group to deal with inquiries from shoppers. Our purpose is "100% client fulfillment by our product high-quality, price tag & our staff service" and enjoy a superb reputation amongst clientele. With quite a few factories, we will provide a wide variety of China Best Voltage Tester Meter Manufacturers – CC1 Series AC Contactor for 9-95A – Changan Group , The product will supply to all over the world, such as: Israel, Niger, Kuwait, Our mission is to deliver consistently superior value to our customers and their clients. This commitment permeates everything we do, driving us to continuously develop and improve our products and the processes to fulfill your needs.
The goods are very perfect and the company sales manager is warmful, we will come to this company to purchase next time.