With a positive and progressive attitude to customer's curiosity, our organization repeatedly improves our products top quality to meet the wants of consumers and further focuses on safety, reliability, environmental necessities, and innovation of Small Push Switch, Residul Circuit Breaker, Earth Leakage Protection Device, "Making the Products of High Quality" is the eternal goal of our company. We make unremitting efforts to realize the goal of "We Will Always Keep in Pace with the Time".
ODM Dual Indicator Light Suppliers – CS2 Series Motor Protection Circuit Breaker – Changan Group Detail:

Description

Electric value: AC690V, 32A, 80A;
Standard: IEC/EN 60947-2, IEC60947-4-1

Type Designation

CS2 SERIES MOTOR PROTECTION  (3)

Operating Condition

3.1 Temperature: -5 ℃~+40℃ ,average temperature in 24 hours not exceed +35 ℃
3.2 Altitude: not exceed 2000m
3.3 Air conditions:
At mounting site, relative humidity not exceed 50% at the max temperature of +40℃, higher
relative humidity is allowable under lower temperature,for example, RH could be 90% at +20℃
3.4 Pollution grade: Grade Ⅲ
3.5 Release grade: 10A(CS2-32) 10A(CS2-80)
3.6 Rated operational system: Continuous operational system
3.7 Mounting conditions:
The inclination between the mounting plane and the vertical plane shall not exceed 5 ° The product shall be installed and operated at a place without obvious shake, Impact and vibration.

Technical Specification

4.1 Protection property

Series No. Multiple of setting current Initial status Time Expected results Ambient temperature
1 1.05 Cold status t≥2h Non-tripping +20℃±2℃
2 1.20 Heat status (right after test.1) t<2h Tripping +20℃±2℃
3 1.50 Heat status (right after test.1) Tripping class 10A t<2min Tripping +20℃±2℃
        10 t<4min    
4 7.20 Cold status Tripping class 10A 2s<t≤10s Tripping +20℃±2℃

Phase failure protection properties

 

Series No.

Multiple of setting current  

Initial status

 

Time

Expected results Ambient temperature
  Any 2 phase The other phase        
1 1.0 0.9 Cold status

t≥2h

Non-tripping +20℃±2℃
2 1.15 0 Heat status

(right after test.1)

t <2h

Tripping +20℃±2℃

Temperature compensation properties

Series No. Multiple of setting current Initial status Time Expected results Ambient temperature
1 1.0 Cold status t≥2h Non-tripping

+40℃±2℃

2 1.2 Heat status (right after test.1) t<2h Tripping  +40℃±2℃
3 1.05 Cold status t≥2h Non-tripping

-5℃±2℃

4 1.3 Heat status (right after test.3) t<2h Tripping  -5℃±2℃
Model of overload relay  Code Rated current (A) Rated ultimate short-circuit breaking capacity Icu(kA) Rated service short-circuit breaking capacity Ics(kA) Standard rated power of three-phase motor (kW)
      230/240V 400/415V 660/690V 230/240V 400/415V 660/690V 230/240V 400/415V 660/690V
CS2-32

3201

0.1~0.16 100 100 100 100 100 100 - - -
 

3202

0.16~0.25 100 100 100 100 100 100 - - -
 

3203

0.25~0.4 100 100 100 100 100 100 - - -
 

3204

0.4~0.63 100 100 100 100 100 100 - - 0.37
 

3205

0.63~1 100 100 100 100 100 100 - - 0.55
 

3206

1~1.6 100 100 100 100 100 100 - - 1.1
 

3207

1.6~2.5 100 100 3 100 100 2.25 0.37 0.75 1.5
 

3208

2.5~4 100 100 3 100 100 2.25 0.75 1.5 3
 

3210

4~6.3 100 100 3 100 100 2.25 1.1 2.2 4
 

3214

6~10 100 100 3 100 100 2.25 2.2 4 7.5
 

3216

9~14 100 15 3 100 7.5 2.25 3 5.5 9
 

3220

13~18 100 15 3 100 7.5 2.25 4 9 11
 

3221

17~23 50 15 3 50 6 2.25 5.5 11 15
 

3222

20~25 50 15 3 50 6 2.25 5.5 11 18.5
 

3232

24~32 50 15 3 50 6 2.25 7.5 12.5 22
 CS2-80

8025

16~25 - 15 - - 7.5 - 5.5 11 -
 

8040

25~40 - 15 - - 7.5 - 11 22 -
 

8063

40~63 - 15 - - 7.5 - 15 33 -
 

8080

56~80 - 15 - - 7.5 - 22 45 -

CS2 MPCB_01
CS2 MPCB_02


Product detail pictures:

ODM Dual Indicator Light Suppliers –  CS2 Series Motor Protection Circuit Breaker – Changan Group detail pictures

ODM Dual Indicator Light Suppliers –  CS2 Series Motor Protection Circuit Breaker – Changan Group detail pictures


Related Product Guide:

We consistently execute our spirit of ''Innovation bringing progress, Highly-quality ensuring subsistence, Administration advertising and marketing gain, Credit history attracting buyers for ODM Dual Indicator Light Suppliers – CS2 Series Motor Protection Circuit Breaker – Changan Group , The product will supply to all over the world, such as: Australia, Casablanca, Israel, We have top engineers in these industries and an efficient team in the research. What is more, we have our own archives mouths and markets in China at low cost. Therefore, we can meet different inquiries from different clients. Please find our website to check more information from our products.
  • We are really happy to find such a manufacturer that ensuring product quality at the same time the price is very cheap.
    5 Stars By Eileen from Argentina - 2017.08.28 16:02
    This company can be well to meet our needs on product quantity and delivery time, so we always choose them when we have procurement requirements.
    5 Stars By Darlene from South Africa - 2017.08.28 16:02
    Write your message here and send it to us