CJ19 Series Capacitor Switching Contactor

Short Description:

CJ19 Contactor for Capacitor Switching,AC50/60Hz,up to 690V;Compatible with Standard IEC/EN 60947-4-1.


Product Detail

Product Tags

Description

Electric value: AC50/60Hz, up to 400V; Standard: IEC/EN 60947-4-1
Ambient temperature:-5℃~+40 ℃,
the average during 24 hours should not exceed +35 ℃; Altitude:≤2000m;
Atmosphere conditions: At mounting site,
relative humidity not exceed 50% at the max temperature of +40℃, higher relative humidity is allowable
under lower temperature. For example, RH could be 90% at +20℃,
special measures should be taken to occurrence of dews; Pollution degree: 3
Installation category: Ⅲ
Installation conditions :
the inclination between installation plane and vertical plane is within ± 5 °
Impact and shake: the products should locate
in the places where there are no obvious impact and shake.

cj

Technical Specification

Standard  

IEC/EN60947-4-1

Model No.  

CJ19-25

CJ19-32

CJ19-43

CJ19-63

CJ19-80

CJ19-95

Rated Conventional Heating Current

Ith (A)

25

32

43

63

80

95

Rated Work Current

415V/Ie (A)

18

25

32

60

80

95

Capacitor Controlled

220V/240V(Kvar)

6

9

10

15

18

22

400V/440V(Kvar)

12

18

20

30

36

40

Rated Insulation Voltage

Ui(V)

690

690

690

690

690

690

Rated Operation Voltage Electrial life(x103 )

Ue(V)

400

400

400

400

400

400

Times

120

120

120

100

100

100

Mechanical life(x103 )

Times

3000

3000

3000

3000

3000

3000

Restrained Surge Capacity

x Ie

15

Auxiliary Contact

Ith=10A

AC-15 360VA;DC-13 33W

Control Capacity

COIL PARAMETERS

Coil Power(VA)

Start-up

76

110

110

230

230

230

Holding

10

11

11

32

32

32

Rated Control Power

Us(V)

24,36,48,110,220,380

Pull time

Ms

12~22

15~24

15~24

20~26

20~35

20~35

Release time

Ms

4~12

5~19

5~19

8~12

6~20

6~20

Operation Range

Pick-up

(85%-110%)Us

Drop-out

(20%-75%)Us

cj1
Model

Amax

Bmax

Cmax

Dmax

E

F

Note

CJ19-25

80

47

124

76

34/35

50/60

 

be fixed with 35mm din rail

CJ19-32

90

58

132

86

40

48

 
CJ19-43

90

58

136

86

40

48

 
CJ19-63

132

79

150

-

-

-

Not only fixed by screws but also could

be fixed with 35mm and 75mm din rail

CJ19-80~95

135

87

158

-

-

-

Wiring and installation
5.1The connection terminals are protected through insulation cover, which is reliable and secure for installation and operation;
5.2For CJ19-25~43, screws are available for installation, as well as the DIN rail; for CJ19-63~95, 35mm or 75mm standard rail are available for installation.


  • Previous:
  • Next:

  • Write your message here and send it to us