Electromagnetic type 10KA RCCB CAL6-100H

Short Description:

CAL6-100H series Residual Current Circuit Breaker suitable for earth leakage protection of 25-100A AC distribution system,large terminal port 35mm²,both side can using pin-type or U-type busbar;High safety performance,over 30 mA current, and power failure in 3 milliseconds;Independently developed and produced all parts and components independently.


Product Detail

Product Tags

Technical Data

Electrical Features

Mode Type
Rated current In Poles
Rated voltage Ue
Insulation voltage Ui Rated frequency Rated residual operation current(I△n)
Rated residual making and breaking capacity (I△m)
Short-circuit current Inc= I△c

Electromagnetic AC,A,G,S 16,25,32,40,63,80,100A
2P(1P+N),4P(3P+N)
2P 240V~
4P 415V~
500V
50/60Hz
30,100,300mA
500A(In≤40A), 10In(In>40A)

SCPD fuse

6,000A/10,000A/

10000

Break time under I△n Rated impulse withstand voltage(1.5/50) Uimp Dielectric test voltage at ind.Freq. for 1min

≤0.1s 4000V
2.5kV

6000

Electrical life Mechanical life

2,000 Cycles 4,000 Cycles

Installation

Contact position indicator Yes
Protection degree

Ambient temperature(with daily average≤35℃)

IP20

-5℃~+40℃

Storage temperature -25℃~+70℃
Terminal connection type Cable/Pin-type busbar
Terminal size top/bottom for cable 35mm2 18-2AWG
Terminal size top/bottom for busbar 35mm2 18-2AWG
Tightening torque 3.0Nm 22In-lbs
Mounting On DIN rail EN60715(35mm) by means of fast clip device
Connection Power supply in both directions

Tripping Current Range

Type

AC

  Tripping current I△/A

0.5I△n<I△<I△n

   

I△n>0.01A

I△n≤0.01A

A

90°

0.35I△n≤I△≤1.4I△n

0.25I△n≤I△≤1.4I△n

0.35I△n≤I△≤2I△n

0.25I△n≤I△≤2I△n

 

135°

0.11I△n≤I△≤1.4I△n

0.11I△n≤I△≤2I△n

VY30N_I8CG02T1]5]VSZZM4